Skip to main content

Enforcement Order EPD-UST-AO-2827

Facility Lulu Mart #2
County Glynn County
Cause of Order Responded failed to ensure cathodic protection testing or test once every 3 years; inspect impressed current cathodic protection system every 60 days; monitor tanks at least every 30 days
Requirements of Order W/in 30 days from the execution of this Administrative Order: conduct a test of the CP system and submit the results to the Division, create a rectifier log and submit the log with the initial rectifier reading to the Division, conduct tank and line tightness testing, initiate SIR monthly monitoring, and submit the tightness testing results to the Division; effective immediately, the UST Registration Certificate for the Respondent's UST facility is suspended and fuel delivery to the Respondent's UST facility is prohibited
Settlement Amount
Legal Authority Underground Storage Tank Act
Date Executed 5‑Jun‑2019
Publication Date For Executed Order 24‑Jun‑2019
File Attachments None